5.10 o: Operator Related Settings
YASKAWA EUROPE SIEP   YASKAWA AC Drive L1000V Technical Manual 151
Parameter Details
5
n o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency.
Note: This parameter is displayed only when the drive is set to allow for user-set units (o1-03 = 3).
n o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the speed reference.
Setting 0: No decimal point
Setting 1: One decimal point
Setting 2: Two decimal points
Setting 3: Three decimal points
u o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
n
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between
LOCAL and REMOTE.
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
n
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator can still be used to stop drive operation when the drive is being
controlled from a remote source (i.e., not from digital operator).
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Up/Down command source is not assigned to the digital
operator. Cycle the Up/Down command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the
values, parameter A1-03 ( Initialize Parameters ) will offer the choice of “1110: User Initialize”. Selecting 1110 resets all
parameters to the user-set default values. Refer to A1-03: Initialize Parameters on page 103 for details on drive
initialization.
No. Name Setting Range Default
o1-10 User-Set Display Units Maximum Value 1 to 60000 Determined by o1-03
No. Name Setting Range Default
o1-11 User-Set Display Units Decimal Display 0 to 3 Determined by o1-03
No. Name Setting Range Default
o2-01 LO/RE Key Function Selection 0 or 1 0
No. Name Setting Range Default
o2-02 STOP Key Function Selection 0 or 1 0
No. Name Setting Range Default
o2-03 User Parameter Default Value 0 to 2 0