4.6 Setup Procedure for Elevator Applications
YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual 89
Start-Up Programming
& Operation
4
u Inspection Operation
n Start Condition in Inspection Operation
Inspection operation is performed when an Up or Down signal is input while one of the following conditions is true:
• Parameter d1-18 is set to 0 or 3 and the selected speed is higher than d1-28 but lower than d1-29.
• Parameter d1-18 is set to 1 or 2 and a digital input programmed for Inspection Operation Speed (H1- = 54) is
enabled.
Inspection Operation uses the same acceleration characteristics and brake sequence at start as normal operation.
The carrier frequency is set to 2 kHz during Inspection Operation, but can be changed using parameter C6-21.
n
Stop Condition in Inspection Operation
To stop the drive during Inspection Operation, either remove the Up or Down command or reset the input terminal for
Inspection Operation.
A deceleration ramp can be set for Inspection Operation using parameter C1-15.
• If C1-15 = 0.00, the drive immediately applies the brake, shuts off the drive output, and opens the motor contactor, i.e.,
the multi-function output terminals set for “Brake Control” (H2- = 50) and “Output Contactor Control” (H2- =
51) are cleared.
• If C1-15 > 0.00, the drive decelerates to stop at the rate set to C1-15, then applies the brake, shuts the output off, and
opens the motor contactor.
n
Inspection Operation Timing Chart
A timing chart for Inspection Operation appears in Figure 4.11.
Figure 4.11 Inspection Operation Sequence
<1> The drive stops if either the Up/Down command or Inspection Operation signals are removed.
Inspection Operation
Speed
DC Injection Braking/
Position Lock at start
DC Injection Braking/
Position Lock at start
Speed
Up/Down command
H1- = 54 (Inspection Operation)
H2- = 51 (Output Cont. Contr.)
H2- = 50 (Brake Control)
Inspection Operation
Speed
Safe disable (terminals H1/H2 on)
and Baseblock off (H1-=8/9)
Speed
Up/Down command
H1- = 54 (Inspection Operation)
H2- = 51 (Output Cont. Contr.)
H2- = 50 (Brake Control)
Safe disable (terminals H1/H2 on)
and Baseblock off (H1-=8/9)
Inspection Operation without Decel Ramp (C1-15=0) Inspection Operation with Decel Ramp (C1-15>0)
<1>
<1>
C1-15