1.4 Checking the LED Indications
1.4.2 218IF-02 Module
1-6
1.4.2 218IF-02 Module
Note:
{
: Unlit,
z
: Lit,
: Flashing,
–
: Indefinite
LEDs at the front of the Ethernet Module
LEDs on the Ethernet connector
RUN ERR
STRX
IP
TX
RX
Ethernet
LINK
100M
Cate-
gory
LED Indication
Indication RemedyModule Front Connector
RUN ERR IP TX RX LINK
Normal
z{z
––
z
Operating normally Normal operation is in progress.
Alarm
z
––
{{ {
No Ethernet connection
Ethernet connection is not estab-
lished.
Check the following.
• Ethernet cables are connected
properly.
• Cables are not broken.
• The power to an Ethernet
device such as a hub that is
connected directly to the
Ethernet Module with an
Ethernet cable is turned on.
z
–
{
–– –
Module configuration definition
not set
Set the module configuration
definition of the 218IF-02 Mod-
ule using MPE720.
Error
––– –
Module fault
Hardware failure has occurred.
Replace the Ethernet Module.
–
––– –