What to do if YASKAWA MP900 Controller MSG-SND function remains BUSY?
- RRichard MitchellAug 20, 2025
If the MSG-SND function remains BUSY and does not end in your YASKAWA Controller, it could be due to the following reasons: * A MSG-SND function parameter setting error. Check that the MSG-SND function parameter settings are correct, especially the remote station number. * Too much traffic on DeviceNet, preventing the sending of the Explicit request message. Try setting a longer communications cycle time. For multi-Master configuration, increase the communications cycle time for other Master.