A.d00
exceeded
the value
set in the
excessive
position
error alarm
level
(Pn520).)
acceleration is too fast.
operate the
SERVOPACK.
Setting of the excessive
position error alarm level
(Pn520) is low against the
operating condition.
Check the alarm level
(Pn520) to see if it is
set to an appropriate
value.
A SERVOPACK fault
occurred.
--
A.d01
Position
Error
Overflow
Alarm at
Servo ON
This alarm occurs if the
servo ON signal (/S-ON) is
turned ON when the
position error is greater
than the set value of Pn526.
Check the position
error amount (Un008)
while the /S-ON signal
is OFF.
A.d02
Position
Error
Overflow
Alarm by
Speed Limit
at Servo ON
When pulses remain in the
error counter, Pn529 limits
the speed if the /S-ON signal
is turned ON. If Pn529 limits
the speed in such a state,
this alarm occurs when
reference pulses are input
and the number of position
errors exceeds the value set
for the excessive position
error alarm level (Pn520).
--
A.d10
Motor-load
Position
Error
Overflow
Motor rotation direction and
external encoder
installation direction are
opposite.
Check the servomotor
rotation direction and
the external encoder
installation direction.
Mounting of the load (e.g.,
stage) and external encoder
joint installation are
incorrect.
Check the external
encoder mechanical
connection.
A.E72
Feedback
Option
Module
Detection
Failure
The connection between the
SERVOPACK and the
Feedback Option Module is
Faulty.
Check the connection
between the
SERVOPACK and the
Feedback Option
Module.
The Feedback Option
Module was disconnected.
--
A Feedback Option Module
fault occurred.
--
A SERVOPACK fault
occurred.
--
A.Eb1
Safety
Function
Signal Input
Timing
Error
The lag between activations
of the input signals /HWBB1
and /HWBB2 for the HWBB
function is ten second or
more.
Measure the time lag
between the /HWBB1
and /HWBB2 signals.
A.F10
Main Circuit
Cable Open
Phase
(With the
main power
supply ON,
voltage was
low for
more than 1
second in
an R, S, or T
The three-phase power
supply wiring is incorrect.
Check the power
supply wiring.
The three-phase power
supply is unbalanced.
Measure the voltage at
each phase of the
three-phase power
supply.
A single-phase power is
input without setting
Pn00B.2 (power supply
method for three-phase
Check the power
supply and the
parameter setting.