<4.  Wiring>
35
IM 01E24A01-01EN
4.4  Connecting to External 
Products of Integral 
Flowmeter and Remote 
Transmitter
4.4.1  Wiring Precautions for Power Supply 
Cables
When connecting to the power supply, observe the points 
below. Failure to comply with these warnings may result 
in an electric shock or damage to the product.
WARNING
 
•  Ensure that the power supply is off in order to prevent 
electric shocks.
•  When opening the cover, wait for more than 20 
minutes after turning off the power.
•  Ensure the protective grounding terminal is grounded 
before turning on the power.
•  Terminate all the cable nish with  round or rod 
shaped crimp terminal (depending on the shape of 
the terminal block) with insulation cover, and connect 
them reliably.
•  Install an external switch or circuit breaker as a 
means to turn the power off (capacitance: 15A, 
conforming to IEC60947-1 and IEC60947-3).  
Locate this switch either near the product or in other 
places facilitating easy operation. Afx a “Power Off 
Equipment” label to this external switch or circuit 
breaker.
WARNING
 
For explosion protection type products, please be sure 
to read the user's manual of the applicable explosion 
protection type as listed in Table 1.1.
Wiring Procedure
1.  Check the product’s power is off, then remove the 
terminal cover (transparent).
2.  Wire the power supply cable and the functional 
grounding cable to the power supply terminals.
3.  Install the terminal cover.
F0423.ai
Functional grounding cable
Power supply 
cable
Functional grounding cable
Power supply 
cable
Integral type or AXW4A remote transmitter
Clamp Type
Integral type or AXW4A remote transmitter
M4 Screw Type
Functional 
grounding
cable
Power supply cable
Figure 4.4.1  Power Cable Wiring
4.4.2  DC Power Connection
When using DC power as the power supply for the 
transmitter, pay attention to the following points.
(1) Connecting Power Supply
IMPORTANT
Do not connect power supply with reversed polarities.
L/+ terminal: connect to + (power supply)
N/– terminal: connect to - (power supply)
Wiring
4