NE107
Status
Error Message
Error Description Countermeasure
Display
C 338:IT2 Not Schedule IT2 Block is not scheduled. Schedule IT2 Block.
C 340:DI1 O/S Mode DI1 Block is in O/S mode.
Change the DI1 Block Mode.Target (DI1.MODE_BLK.Target) to Auto
or other mode.
C 341:DI1 Man Mode DI1 Block is in Man mode.
Change the DI1 Block Mode.Target (DI1.MODE_BLK.Target) to Auto
or other mode.
C 342:DI1 Not Schedule DI1 Block is not scheduled. ScheduleDI1 Block.
C 343:DI1 Simulate Act DI1 block is in simulation mode.
Change the DI1 Simulation En/Disable (DI1.SIMULATE.SIMULATE_
ENABLE) to Disabled.
C 344:DI2 O/S Mode DI2 Block is in O/S mode.
Change the DI2 Block Mode.Target (DI2.MODE_BLK.Target) to Auto
or other mode.
C 345:DI2 Man Mode DI2 Block is in Man mode.
Change the DI2 Block Mode.Target (DI2.MODE_BLK.Target) to Auto
or other mode.
C 346:DI2 Not Schedule DI2 Block is not scheduled. ScheduleDI2 Block.
C 347:DI2 Simulate Act DI2 block is in simulation mode.
Change the DI2 Simulation En/Disable (DI2.SIMULATE.SIMULATE_
ENABLE) to Disabled.
C 348:DI3 O/S Mode DI3 Block is in O/S mode.
Change the DI3 Block Mode.Target (DI3.MODE_BLK.Target) to Auto
or other mode.
C 349:DI3 Man Mode DI3 Block is in Man mode.
Change the DI3 Block Mode.Target (DI3.MODE_BLK.Target) to Auto
or other mode.
C 350:DI3 Not Schedule DI3 Block is not scheduled. ScheduleDI3 Block.
C 351:DI3 Simulate Act DI3 block is in simulation mode.
Change the DI3 Simulation En/Disable (DI3.SIMULATE.SIMULATE_
ENABLE) to Disabled.
C 352:AR O/S Mode AR Block is in O/S mode.
Change the AR Block Mode.Target (AR.MODE_BLK.Target) to Auto
or other mode.
C 353:AR Man Mode AR Block is in Man mode.
Change the AR Block Mode.Target (AR.MODE_BLK.Target) to Auto
or other mode.
C 354:AR Not Scheduled AR Block is not scheduled. Schedule AR Block.
C 359:No FB Scheduled No Function Block is scheduled. Schedule Function Block or check the LAS communication.
C 360:STB O/S Mode Sensor Transducer Block is in O/S mode.
Change the STB Block Mode.Target (STB.MODE_BLK.Target) to
Auto mode.
C 361:DTB O/S Mode Diagnostic Transducer Block is in O/S mode.
Change the DTB Block Mode.Target (DTB.MODE_BLK.Target) to
Auto mode.
C 362:MTB O/S Mode Maintenance Transducer Block is in O/S mode.
Change the MTB Block Mode.Target (MTB.MODE_BLK.Target) to
Auto mode.
C 363:LTB O/S Mode LCD Transducer Block is in O/S mode.
Change the LTB Block Mode.Target (LTB.MODE_BLK.Target) to Auto
mode.
<7. Errors and Countermeasures (Display unit)>
66
IM 01E24A01-01EN

Other manuals for YOKOGAWA AXW4A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA AXW4A and is the answer not in the manual?

YOKOGAWA AXW4A Specifications

General IconGeneral
BrandYOKOGAWA
ModelAXW4A
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals