<1. INTRODUCTION AND GENERAL DESCRIPTION>
1-13
IM 12A01A02-01E 8th Edition : Oct. 01, 2015-00
C22.2 No213-M1987 Non-incendive Electrical Equipment for Use in Class I, Division 2
Hazardous Locations
CAN/CSA-E60079-0-07 Electrical apparatus for explosive gas atmospheres
- Part 0: General requirements
CAN/CSA-E60079-11-02 Electrical apparatus for explosive gas atmospheres
- Part 11: Intrinsic safety “i”
IEC 60529:2001 Degrees of protection provided by enclosures (IP Code)
Type of protection (C22.2)
Class I, Division 1, Groups A, B, C and D (Intrinsically Safe)
Class I, Division 2, Groups A, B, C and D (Nonincendive)
For all protection type,
T4: for ambient temperature: -20 to 55°C
T6: for ambient temperature: -20 to 40°C
Atmosphere pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
Ambient Humidity: 0 to 100% (No condensation)
Degree of Protection of the Enclosure: Type 4X
Type of protection (E60079)
Ex ia IIC
T4: for ambient temperature: -20 to 55°C
T6: for ambient temperature: -20 to 40°C
Atmosphere pressure: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
Ambient Humidity: 0 to 100% (No condensation)
Degree of Protection of the Enclosure: IP66
NEPSI Intrinsic safety approval
Applicable standard
GB 3836.1-2010 Explosive atmospheres-Part 1: Equipment - General requirements
GB 3836.4-2010 Explosive atmospheres-Part 4: Equipment protection by intrinsic safety “i”
GB 3836.20-2010 Explosive atmospheres-Part 20: Equipment with equipment
protection level (EPL) Ga
Type of protection
Ex ia IIC Ga
T4: for ambient temperature: -20°C to 55°C
T6: for ambient temperature: -20°C to 40°C
Atmosphere pressure: 80kPa (0.8bar) to 110 kPa (1.1bar)
Degree of Protection of the Enclosure: IP66
Electrical Parameters (Ex ia)
Each housing assembly (base module) and each sensor module are respectively certicated.
Input parameters of sensor module meet output parameters of housing assembly.
Housing assembly
Input parameters Supply and output circuit (terminals + and -):
Ui, Vmax = 30 V
Ii, Imax = 100 mA
Pi, Pmax = 0.75 W
Ci =13 nF
Li = 0 mH
(Linear source)
Output parameters Sensor module input circuit (CN2 or CN3 on Back board)
Uo Vt, Voc = 13.65 V
Io, It, Isc = 50 mA
Po = 0.372 W
Co, Ca = 80 nF
Lo, La = 7.7mH
1
PH
SC
ISC
DO
SENCOM