40
IM MY600-01EN
ATTENTION
Toujoursdébrancherl’alimentationdel’équipementtesté
avant de commencer la mesure de l’isolation. Ne pas 
faire des mesures sur un circuit sous tension. Sinon, cela 
pourrait endommager l’appareil.
Note
• DependingontheDUT,theindicatedinsulationresistance
may not be stable.
• Theinstrumentmayproducesoundsduringainsulation
resistance measurement, but this is not a malfunction.
• MeasurementsmaytakelongerwhentheDUTisa
capacitive load.
• TheinstrumentoutputspositivevoltagefromtheEARTH
terminal and negative voltage from the LINE terminal.
• Whenmakingameasurement,connecttheEARTH
terminal to the ground terminal. Generally, connecting the 
positive terminal to ground when measuring the insulation 
resistance to ground or measuring the insulation resistance 
when one end of the DUT is grounded is more suitable for 
detecting insulation failures.
Measurement Procedure
1. 
Connect the probes as shown in the following figure.
  •Insert98008intotheLINEterminal.
  •Insert98009intotheEARTHterminal.
 
 
600 V MAX
Black (98009) Red (98008)