45
IM MY600-01EN
This value is calculated by dividing the rated voltage by
ratedcurrent.Iftheratingis500V,forexample,thelower
limitiscalculatedas500V÷1mA=0.5MΩ.Thatis,an
insulationresistanceof0.5MΩormoreisrequiredto
provide the rated voltage to the instrument.
Rated voltage
50
V 100
V 125
V 250
V 500
V 1000V
Lower limit of
the insulation
resistance to
provide the
rated current of
1 mA
0.05MΩ 0.1MΩ 0.125
MΩ
0.25MΩ 0.5MΩ 1MΩ
Signal input voltage (V)
1000
800
600
400
200
1000 V
range
500 V
range
1200
1000
Insulation resistance (MΩ)
250 V
range
125 V
range
100 V
range
50 V
Range
100
200
50
300
250
125
150
Signal input voltage (V)
Insulation resistance (MΩ)