SECTION 5 - COMMISSIONING
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
FORM 155.31-CL1.EN.UL
ISSUE DATE: 12/14/2018
DOUBLE EFFECT STEAM ABSORPTION CHILLER COMMISSIONING DATA SHEET (2/2)
User:
Model: MFG.No.: User's machine code:
Running Data
Date: Measured by Specification Standard : : :
Steam
Steam control valve or
steam drain control valve
position
% Control panel
Steam primary pressure Pressure gauge ≤ 116PSI
Steam secondary pres-
sure
Pressure gauge
Steam temperature °F Thermometer ≤347°F
Drain outlet (back)
pressure
Pressure gauge
Drain temperature °F Thermometer ≤ 203°F
Steam consumption Flow meter
Chilled
Water
Inlet temperature °F Control panel
Outlet temperature °F Control panel
Inlet pressure Pressure gauge
Outlet pressure Pressure gauge
[3] Pressure drop DPG or calculation [4]
[1] Flow rate FM or calculation [2]
Cooling
Water
Inlet temperature °F Control panel 68.0~89.6°F
Outlet temperature °F Control panel 68.0~99.5°F
Inlet pressure Pressure gauge
Outlet pressure Pressure gauge
[7] Pressure drop DPG or calculation [8]
[5] Flow rate FM or calculation [6]
Absorption
Cycle
HG pressure (Gauge) PSIG Compound gauge
≤ -0.4 PSIG
HG pressure (Sensor)
mmHg
Control panel
≤ 720 mmHg
HG temperature °F Control panel ≤329°F
HG solution concentra-
tion
% Control panel
Absorber temperature °F Control panel
Refrigerant temperature °F Control panel
Liquid
Level
HG Level gauge
LG Level gauge
Absorber Level gauge
Evaporator (Lower) Level gauge
Evaporator (Upper) Level gauge
NOTES:
Operating hours hours
Number of purge times times
Fill out each specication pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If ow meter (FM) is not available, calculate each ow rate as below.
[1] = [2] x √[3]/[4] [5]=[6] x √[7]/[8]
LD20020
Same
Height
OUT
P P
IN
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
ft3/h
ft3/h
ft3/h