JOHNSON CONTROLS
97
SECTION 5 - COMMISSIONING
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
Chiller
Chilled water pump
Sequential
Operation
AND
Air conditioner
Cooling water pump Cooling tower
Sequential
Operation
AND
Interlock
Sequential
operation
(2)
(3)
Sequential
operation
Interlock
Other interlocks, including earthquake sensor, abnormal room temperature sensor or other relevant sensors.
NOTES:
1. Be sure to implement sequential operation of the chilled water pump and the cooling water pump from the chiller.
2. If there is only one air conditioner, secure interlock for the air conditioner operation (the part indicated by broken lines).
3. Implement sequential operation in such a way that when the chilled water pump stops, the cooling water also stops.
4. If the chilled and cooling water system is the common system, you must install the isolation valve on the chilled water and cooling water
inlet pipe entering the chiller, and interlock these isolation valves with the chiller control panel. This is imperative for safe and reliable opera-
tion of the chiller as well as to prevent potential crystallization of lithium bromide solution and freezing of the evaporator tubes.
FIGURE 38 - STEAM SEQUENTIAL OPERATION FLOWCHART
Not completed
AND
Chiller dilution
operation begins
Chiller dilution
operation completed
Stop the absorption
chiller
Completed
Air conditioner and
chilled water pump stop
NOTE: Verify that the air conditioner has stopped after the chiller
dilution operation is complete. Otherwise, the chiller may
become damaged due to freezing of the chilled water and/
or crystallization of the solution.
Close the steam supply main valve and steam drain manual
valve once the unit has stopped.
Stop the air
conditioning system
FIGURE 39 - STOPPING ABSORPTION CHILLER STEAM FLOWCHART