EasyManua.ls Logo

York YHAU-CW - Chilled Water Overcooling or Refrigerant Overcooled

York YHAU-CW
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
158
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
SECTION 8 – TROUBLESHOOTING
TABLE 35 - TROUBLESHOOTING THE HIGH
TEMPERATURE GENERATOR
ITEM CAUSE COUNTERMEASURE
1
Cooling water is Insufcient
or suspended.
See if the cooling water supply rate conforms to the specication. Check the ow
meter, discharge pressure of the cooling water pump, current,and other applicable
pumps or pressures.
If the ow rate is insufcient, check the opening ratio of the ow controller valve
and check the strainer for clogging.
2
Cooling water temperature
at inlet is high.
Check the capacity of the cooling tower.
3
Non-condensable gas stays
in the machine.
• Check the capacity of the vacuum pump.
• Check the purge unit.
Purge air from the chiller (See SECTION 7 – MAINTENANCE).
If partial load operation is continued for a long period, non-condensable gas tends
to stay in the absorber. In this case, purge directly from the low pressure side
(according to instructions in SECTION 7 – MAINTENANCE).
4
Heat exchange tube is
dirty (chilled water, cooling
water).
Contact your local Johnson Controls Service Ofce.
5 Solution is crystallized.
6 Corrosion inhibitor is worn.
7
Air leaks in absorption
chiller.
TABLE 36 - CHILLED WATER OVERCOOLING OR
REFRIGERANT OVERCOOLED
ITEM CAUSE COUNTERMEASURE
1
Chilled water ow rate
lowers or changes sharply.
See if the chilled water ow rate changes sharply (particularly in the case
of variable ow rate specication). If it changes sharply, apply a limit of the
change rate to the chilled water ow control or take another measure.
2
Cooling water temperature
at inlet changes sharply.
See if the cooling water temperature at inlet changes sharply. Checking the
start and stop of the fan).
If the chiller refrigerant temperature is low, the chiller stops immediately but
does not perform the diluting operation. If left as it is, the solution may be
crystallized in 4-5 hours. To prevent this, dilute the solution according to the
procedure shown in Manual Refrigerant Blow Down and Diluting Method on
page 137.
3 Load lowers sharply. See if the load changes sharply.
4
Refrigerant is dirty
(contains solution).
See if the refrigerant rening operation has been performed. For the refrigerant
rening method, see NOTE: Do not loosen the bolts around the ange or
remove the disk from the holder. If the disk is removed for any reason, it must
be replaced with a new one! on page 30
5
Heat exchange tube is
dirty (Chilled water).
Contact your local Johnson Controls Service Ofce.
6
Temperature controller or
safety switch is broken.

Table of Contents

Related product manuals