EasyManua.ls Logo

York YHAU-CW - Hoisting the Machine

York YHAU-CW
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
23
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
3
HOISTING THE MACHINE
When hoisting the machine, attach a shackle to each of
the four eye plates and lift the machine using care that
the angle formed by the wire is within 60 degrees as
shown in the figure below.
Use care not to apply shock to the machine. The ma-
chine is a high-vacuum vessel containing a corrosive
solution. Use diligence in protecting the machine as
repair is labor intensive and costly.
Be sure to lift the machine horizontally. If the machine
is inclined, the solution and refrigerant inside will shift
producing an offset load. This can cause damage to the
machine and pose a risk to the machine installer or per-
sons moving the unit.
FIGURE 4 - HOISTING PROCEDURES
LD22945_UL
This angle must
be within 60°
EYE PLATE
EYE PLATE
1.96
1.25
3.14
2.94