JOHNSON CONTROLS
21
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
3
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
LD18119
FIGURE 3 - WARNING
Rigging and lifting should only be done by
a professional rigger in accordance with a
written rigging and lifting plan. The most
appropriate rigging and lifting method
will depend on job specic factors, such as
the rigging equipment available and site
needs. Therefore, a professional rigger
must determine the rigging and lifting
method to be used, and it is beyond the
scope of this manual to specify rigging
and lifting details.
This chiller is for air conditioning or a cooling manu-
facturing process. Transport, store, and use this chiller
under the following conditions:
Installation location: Indoor, non-explosion area
Ambient temperature: 50 ~ 104 °F
Humidity: 10 ~ 90% (RH%)
Altitude: 3333 feet or lower
If the temperature in the plant room drops below 50 °F,
you must have the cold ambient option.