SECTION 6 - COMMISSIONING
JOHNSON CONTROLS
101
Form 201.28-NM1.1
Issue date: 08/06/2021
6
A. 
the lowest possible ambient temperature must be

......-or-
B.         
completing the following steps:
Remove the power to the water box heaters

Drain the evaporator
Leave the evaporator drain valves open

used but continuous power to the chiller control panel,

be guaranteed during periods of subfreezing ambient
temperatures, then one of the freeze damage protec-
tion protocols in the following table must be followed:
Table 11 - YVAA freeze damage protection requirements
Chiller control of chilled fluid
circuit pumps
Actuated suction service
isolation valve
Water box immersion heaters
Ambient air temperatures from
32⁰F (0⁰C) down to 0⁰F (-17.8⁰C)
Required if actuated suction
service isolation valve is not
selected
Required if chilled fluid pumps are
not controlled by chiller control
panel
Not required
Ambient air temperatures below
0⁰F (-17.8⁰C) down to -20⁰F
(-28⁰C)
Required Required Required