R-513A conversion table
The following table can be used for conversion of refriger-
ant R-513A from pressure to saturated temperature.
Table 28 - R-513A refrigerant pressure to saturated temperature
Pressure
(psig)
Temperature
average (°F)
Pressure
(psig)
Temperature
average (°F)
Pressure
(psig)
Temperature
average (°F)
Pressure
(psig)
Temperature
average (°F)
0 -20.5 130 99.3 260 146.7 390 179.1
5 -8.4 135 101.6 265 148.1 395 180.2
10 1.4 140 103.9 270 149.6 400 181.2
15 9.8 145 106.1 275 151.0 405 182.3
20 17.2 150 108.3 280 152.4 410 183.3
25 23.8 155 110.4 285 153.7 415 184.3
30 29.8 160 112.4 290 155.1 420 185.4
35 35.3 165 114.5 295 156.4 425 186.4
40 40.4 170 116.4 300 157.7 430 187.4
45 45.1 175 118.4 305 159.0 435 188.4
50 49.5 180 120.3 310 160.3 440 189.4
55 53.7 185 122.2 315 161.6 445 190.3
60 57.7 190 124.0 320 162.9 450 191.3
65 61.5 195 125.8 325 164.1 455 192.2
70 65.1 200 127.6 330 165.3 460 193.2
75 68.5 205 129.3 335 166.6 465 194.1
80 71.9 210 131.0 340 167.8 470 195.1
85 75.0 215 132.7 345 168.9 475 196.0
90 78.1 220 134.3 350 170.1 480 196.9
95 81.0 225 136.0 355 171.3 485 197.8
100 83.9 230 137.6 360 172.4 490 198.7
105 86.6 235 139.1 365 173.6 495 199.6
110 89.3 240 140.7 370 174.7 500 200.4
115 91.9 245 142.2 375 175.8 505 201.3
120 94.4 250 143.7 380 176.9
125 96.9 255 145.2 385 178.0
Notes:
1. Temperature data is mean of vapor temperature and liquid temperature.
2. Source of the tabulated data above: REFPROP 9.1214, R513a.MIX, HMX.BNC from Chemours, saturation table.
Data generated by Justin P. Kauffman on and as of 07/29/2016.