SECTION 8 - MICROPANEL
Form 201.28-NM1.1
Issue date: 08/06/2021
Table 23 - Setpoint limits
Program value Mode Low limit High limit Default
Leaving chilled liquid setpoint
Water cooling
40.0°F 60.0°F 44.0°F
4.4°C 15.6°C 6.7°C
Glycol cooling
15.0°F 70.0°F 44.0°F
-9.4°C 15.6°C 6.7°C
Leaving chilled liquid control range
1.5°F 2.5°F 2.0°F
0.8°C 1.4°C 1.1°C
Maximum remote temperature reset
2°F 40°F 20°F
1°C 22°C 11°C

the setpoints displays.
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
Table 23 on page 150.