York YVAA Style A - YVAA Native Communications Data Map; Analog and Binary Write Points

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
114
SECTION 7 - OPERATION
Form 201.28-NM1.1
Issue date: 08/06/2021
Table 14 - YVAA native communications data map
Item
1
2
3
4
5
6
7
8
9
10
Imperial SI Point List Description 1 2 3 4 5 6 7 8 9 10
1 REM_SETP AV1 1026 03,06,16 Div 10 ADF 1 °F °C Remote Setpoint (Start cmd must be active to take effect) S S S S S S
2 DMD_LIMIT AV2 1027 03,06,16 Div 10 ADF 2 % FLA % FLA
Remote Current Limit Setpoint (Start cmd must be active
to take effect)
SSSSSS
3 SND_LIMIT AV3 1028 03,06,16 Div 10 ADF 3 % %
Remote Sound Limit (RSL option must be enabled or point
ignored)
SSSSSS
4 SPARE AV1 AV4 1029 03,06,16 Div 10 ADF 4 None None Spare NNNNNN
5 START_STOP BV1 1538 01,03,05,06,15 N/A BD 1 0/1 0/1 Remote Start / Stop Command [0=Stop, 1=Run] S S S S S S
6 SPARE_BV1 BV2 1539 01,03,05,06,15 N/A BD 2 0/1 0/1 Spare NNNNNN
7 SPARE_BV2 BV3 1540 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare NNNNNN
8 SPARE_BV3 BV3 1541 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare NNNNNN
9 LCHLT AI1 514 03,04 x10 ADF 5 °F °C Leaving Chilled Liquid Temperature S S S S S S
10 ECHLT AI2 515 03,04 x10 ADF 6 °F °C Entering Chilled Liquid Temperature S S S S S S
11 EV_ELT AI3 516 03,04 x10 ADF 7 °F °C Evaporator Entering Liquid Temperature (Free Cooling) O O O O O O
12 VSD_IA_TEMP AI4 517 03,04 x10 ADF 8 °F °C VSD Internal Ambient Temperature S S S S S S
13 S1_COND_TEMP AI5 518 03,04 x10 ADF 9 °F °C Sys 1 Condenser Temperature S S S S S S
14 S2_COND_TEMP AI6 519 03,04 x10 ADF 10 °F °C Sys 2 Condenser Temperature S S S S S S
15 S1_DSCH_TEMP AI7 520 03,04 x10 ADF 11 °F °C Sys 1 Discharge Temperature S S S S S S
16 S2_DSCH_TEMP AI8 521 03,04 x10 ADF 12 °F °C Sys 2 Discharge Temperature S S S S S S
17 OAT AI9 522 03,04 x10 ADF 13 °F °C Ambient Air Temperature SSSSSS
18 S1_EDT_TEMP AI10 523 03,04 x10 ADF 14 °F °C Sys 1 Eductor Temperature S O O O O O
19 S2_EDT_TEMP AI11 524 03,04 x10 ADF 15 °F °C Sys 2 Eductor Temperature S O O O O O
20 S1_OIL_PRESS AI12 525 03,04 x10 ADF 16 PSI BAR Sys 1 Oil Pressure SSSSSS
21 S2_OIL_PRESS AI13 526 03,04 x10 ADF 17 PSI BAR Sys 2 Oil Pressure SSSSSS
22 S1_SUCT_PRES AI14 527 03,04 x10 ADF 18 PSI BAR Sys 1 Suction Pressure SSSSSS
23 S2_SUCT_PRES AI15 528 03,04 x10 ADF 19 PSI BAR Sys 2 Suction Pressure SSSSSS
24 S1_DSCH_PRES AI16 529 03,04 x10 ADF 20 PSI BAR Sys 1 Discharge Pressure SSSSSS
25 S2_DSCH_PRES AI17 530 03,04 x10 ADF 21 PSI BAR Sys 2 Discharge Pressure SSSSSS
26 S1_MC_FLA AI18 531 03,04 x10 ADF 22 % % Sys 1 Motor Current FLA SSSSSS
27 S2_MC_FLA AI19 532 03,04 x10 ADF 23 % % Sys 2 Motor Current FLA SSSSSS
28 S1_OP_HRS AI20 533 03,04 x1 ADF 24 None None Sys 1 Operating Hours SSSSSS
29 S2_OP_HRS AI21 534 03,04 x1 ADF 25 None None Sys 2 Operating Hours SSSSSS
30 S1_COMP_ST AI22 535 03,04 x1 ADF 26 None None Sys 1 Compressor Starts SSSSSS
31 S2_COMP_ST AI23 536 03,04 x1 ADF 27 None None Sys 2 Compressor Starts SSSSSS
32 S1_HI_MTR_T AI24 537 03,04 x10 ADF 28 °F °C Sys 1 Highest Motor Temperature S S S S S S
Updated points and codes
YVAA, YVFA, YAGK
Board: 031-03478Native Modbus RTU, BACnet MS/TP, N2 Data Map
Comments
Y.ACS.20.02
Version York P/N
Y.ACS.20.06 - Y.ACS.20.10
Y.ACS.20.12 - Y.ACS.20.14
Y.ACS.20.15 - Y.ACS.20.17
031-03476-010
031-03476-010
031-03476-010
031-03476-010
031-03476-010
Y.ACS.20.04 - Y.ACS.20.05
N2 Metasys
Y.ACS.20.18
Modbus Data Type
Supported
Modbus
Scaling
(See
Note 5)
New
Updated
Updated
Updated
Updated points and codes
031-03476-010
Item
Ref
Num
BACnet Name
BACnet
Object
Instance
Modbus
Address
ANALOG READ ONLY POINTS
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
ANALOG WRITE POINTS
BINARY WRITE POINTS
YVAA YVFA YAGK Native 13 May 21
Property of Johnson Controls
Subject to change without notice.
1 of 5