JOHNSON CONTROLS
52
SECTION 4 - INSTALLATION
Form 201.28-NM1.1
Issue date: 08/06/2021
Table 4 - Electrical lug data
Field wiring lugs
Standard and ultra quiet condenser fans
Terminal block Circuit breaker
Non-fused disconnect
switch
YVAA MODEL
Input
volts
Input
freq
Wires
per
phase
Lug wire range
Wires per
phase
Lug wire range
Wires per
phase
Lug wire
range
Frame Cond Evap
Single point wiring
015 3 B
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
016 5 B
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
017 8 C
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
018 3 A
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
019 5 A
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
019 8 B
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
020 0 C
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
021 3 A
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
021 5 C
200 60 4 #2 - 600 kcmil
230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil
380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil
575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil