SECTION 4 - INSTALLATION
JOHNSON CONTROLS
51
Form  201.28-NM1.1
Issue date: 08/06/2021
4
Connect the 115 V/60 Hz or 220 V/50 Hz power sup-
ply to the top terminals of the 2-pole-breaker, as shown 
in Figure 20. Connect the hot line to terminal H and 
the neutral line to terminal N. After connecting the ter-
minals, turn on the breaker only when the evaporator 
is filled with water in waterside. The recommended 
power supply wiring size is 18-4-AWG.
Before turning on the breaker, make sure 
the evaporator is lled with water. Misop-
eration will void warranty and a water box 
heater fail, which will lead to the freezing 
of the evaporator.
Evaporator heaters used in the unit may 
malfunction without alarm. Once the 
heater failure is found under subfreezing 
condition, stop using the chiller and drain 
o water from the evaporator completely 
to protect the evaporator from freezing.