SECTION 5 - TECHNICAL DATA
Form 201.28-NM1.1
Issue date: 08/06/2021
Elastomeric isolator installation
Read the following instructions before beginning
installation.
1. Isolators are shipped fully assembled and are to be
positioned in accordance with the submittal draw-
ings or as otherwise recommended.
2.        -
base, ensuring that all isolators lines match the
equipment mounting holes. The VMC group
recommends that the isolator base (A) be installed
on a level surface. Shim or grout as required,
leveling all isolator bases to the same elevation

tolerated).
3. Bolt or anchor all isolators to supporting structure
utilizing base thru holes (B).
4. Remove top bolt and top washer. Place equip-
ment on top of isolators so that mounting holes in
equipment or base line up with threaded hole (C).
5. Reinstall top bolt and washer and tighten down.