EasyManua.ls Logo

York YVAA Style A - Minimum Installation Clearances; Recommended Clearances; Evaporator Tube Removal Clearances

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
36
SECTION 4 - INSTALLATION
Form 201.28-NM1.1
Issue date: 08/06/2021
Recommended minimum clearances
Recommended clearances for the YVAA units are:
Side to wall – 6 ft (1.8 m)
Rear to wall – 6 ft (1.8 m)
Control panel end to wall – 4 ft (1.2 m)
Top – no obstructions whatsoever
Distance between adjacent units – 10 ft (3 m)
Figure 5 - Acceptable minimum clearances around
and between units
1.8 m (6
ft)
Minimum
1.2 m (4 ft)
Minimum
3 m (10
ft)
Minimum
Control panel
C
A
A
Tube Removal
Clearance Area
Tube Removal
Clearance Area
B
Clearance dimensions provided in
Figure 5 on page 36 and Table 2 on
page 36 are necessary to maintain good
airow and ensure correct unit opera-
tion. It is also necessary to consider ac-
cess requirements for safe operation and
maintenance of the unit and power and
control panels. Local health and safety
regulations, or practical considerations
for service replacement of large compo-
nents, may require larger clearances than
those recommended.
Table 2 - Minimum evaporator tube removal clearance
Model YVAA
Tube removal
clearance dimensions
A B C
Frame Cond Evap in. mm in. mm in. mm
015 3 B 26 663 36 914 132 3353
016 5 B 26 663 36 914 132 3353
017 8 C 26 663 36 914 156 3962
018 3 A 26 663 36 914 144 3658
019 5 A 26 663 36 914 144 3658
019 8 B 26 663 36 914 144 3658
020 0 C 26 663 36 914 156 3962
021 3 A 26 663 36 914 156 3962
021 5 C 26 663 36 914 156 3962
021 8 C 26 663 36 914 156 3962
023 3 B 26 663 36 914 132 3353
024 5 C 26 663 36 914 156 3962
024 8 C 26 663 36 914 156 3962
026 3 B 26 663 36 914 132 3353
027 0 D 26 663 36 914 192 4877
027 3 D 26 663 36 914 192 4877
027 5 E 26 663 36 914 192 4877
027 8 E 26 663 36 914 192 4877
029 5 E 26 663 36 914 192 4877
030 3 C 26 663 36 914 156 3962
030 5 E 26 663 36 914 156 3962
030 8 E 26 663 36 914 156 3962
031 8 E 26 663 36 914 192 4877
032 3 E 26 663 36 914 192 4877
033 3 C 26 663 36 914 156 3962
034 3 E 26 663 36 914 192 4877
034 5 E 26 663 36 914 192 4877
036 8 J 26 663 36 914 192 4877
037 3 F 26 663 36 914 144 3658
037 5 J 26 663 36 914 192 4877
039 8 J 26 663 36 914 192 4877
041 3 H 26 663 36 914 192 4877
042 5 H 26 663 36 914 144 3658
042 8 J 26 663 36 914 192 4877
044 3 G 26 663 36 914 144 3658
047 5 J 26 663 36 914 192 4877
048 3 G 26 663 36 914 144 3658
049 0 K 26 663 36 914 192 4877
050 0 J 26 663 36 914 192 4877
052 3 J 26 663 36 914 192 4877

Table of Contents