SECTION 7 - OPERATION
JOHNSON CONTROLS
107
Form  201.28-NM1.1
Issue date: 08/06/2021
7
Power supply test points
TP1 GND (Measure TP2, TP3, TP4 and TP5 in  
reference to this Test Point).
TP2 +3.3 V [3.2 VDC to 3.4 VDC] provides power to 
the processors.
TP3 +5 V [4.8 VDC to 5.2 VDC] power communica-
tion ports 2,3 and 4 and analog sensors.
TP4 +12 V [11.64 VDC to 12.36 VDC] powers the dis-
play and backlight and is regulated to become the +5 V.
TP5 +15 V [11.3 VDC to 16.6 VDC] powers the analog 
outputs to the EEV valves.
Configuration jumpers 
The same configuration jumpers that existed on the 
02478 are provided on the 03478.
JP4 Remote Temp Reset jumper position Pins 1 to 2 
(left) = 4 mA to 20 mA, Pins 2 to 3 (right) = 0 VDC to 
10 VDC.
JP5 Remote Current Limit jumper position Pins 1 to 2 
(left) = 4 mA to 20 mA, Pins 2 to 3 (right) = 0 VDC to 
10 VDC.
JP6 Remote Sound Limit jumper position (Pins 1 to 2 
(left) = 4mA to 20 mA, Pins 2 to 3 (right) = 0 VDC to 
10 VDC.