SECTION 8 - MICROPANEL
Form  201.28-NM1.1 
Issue date: 08/06/2021
UNIT  STATUS 
 UNIT  SWITCH  OFF  SHUTDOWN
This message indicates the UNIT SWITCH is in the 
OFF position and not allowing the unit to run.
UNIT  STATUS 
 DAILY  SCHEDULE  SHUTDOWN
This message indicates that either the daily or holi-
day schedule programmed is keeping the chiller from  
running.
UNIT  STATUS
 REMOTE  CONTROLLED  SHUTDOWN
This message indicates that either an ISN or RCC has 
turned the chiller OFF and is not allowing it to run.
UNIT  STATUS
 FLOW  SWITCH  SHUTDOWN
This message indicates the flow switch is not allowing 
the chiller to run. There is a 1 second delay on this safety 
to ensure the flow switch did not momentarily open.
UNIT  STATUS 
 VSD  COOLING  SHUTDOWN
This message indicates the chiller is shutdown, but 
running all the condenser fans, VSD glycol pump, and 
VSD fan in an effort to bring the internal VSD ambient 
temperature down to an acceptable level before allow-
ing the chiller to start.
SYS  X  REMOTE  RUN  CONTACT  IS  OPEN
This message indicates the remote start / stop contact 
between 2 and 15 or 2 and 16 of the 1TB terminal block 
is open. There is a 1 second delay on this safety to en-
sure the remote contacts did not momentarily open.
SYS  X  SYSTEM  SWITCH  IS  OFF
This message indicates the system switch (software using 
keypad) is turned OFF. The system will not be allowed to 
run until the system switch is turned ON using the keypad.
SYS  X  NOT  RUNNING
This message indicates the system is not running be-
cause the chilled liquid is below the setpoint or the 
micro has not loaded the lead system far enough into 
the loading sequence to bring the lag system ON. This 
message will be displayed on the lag system until the 
loading sequence is ready for the lag system to start.
SYS  X  COOLING  DEMAND  SHUTDOWN
This message is only displayed in the Normal Shut-
down History display to indicate a capacity control 
shutdown.
SYS  X  COMPRESSOR  RUNNING
This message indicates the system is running as a result 
of cooling demand.
SYS  X  SHUTTING  DOWN
The compressor shutting down message indicates the re-
spective system is ramping down in speed before shut-
ting OFF. This message is displayed after the software 
run signal is disabled until the VSD notifies the Chiller 
Control Board the compressor is no longer running.
SYS  X  ANTI-RECYCLE  TIMER    = XXX SEC
This message indicates the amount of time left on the 
respective system anti-recycle timer and the system is 
unable to start until the timer times out.
SYS  X  DISCHARGE  PRESSURE  LIMITING
The Discharge Pressure Limiting message indicates 
the discharge pressure load limit or discharge pressure 
unloading is in effect.
SYS  X  SUCTION  PRESSURE  LIMITING
The Suction Pressure Limiting message indicates the 
suction pressure load limit or suction pressure unload-
ing is in effect.
SYS  X  MOTOR TEMP LIMITING
The Motor Temp Limiting message indicates the motor 
temp load limit or motor temp unloading is in effect.
SYS  X  MOTOR CURRENT  LIMITING
The motor current limiting message indicates the mo-
tor current load limit or motor current unloading is in 
effect.