SECTION 8 - MICROPANEL
JOHNSON CONTROLS
159
Form  201.28-NM1.1
Issue date: 08/06/2021
8
the  (ENTER) key. The cursor will then move to the 
AM/PM selection. The meridian (AM/PM) value may 
ARROW) keys and entered by pressing  (ENTER) 
key. Repeat this process for the STOP time. Once a 
schedule is entered, the schedule for the next day will 
appear. The start and stop time of each day may be pro-
grammed differently.
To view the schedule without making a change, sim-
ply press the SCHEDULE key until the day you wish 
backwards to the previous screen.
If at any time the schedule is changed for 
Monday, all the other days will change to 
the new Monday schedule. This means if 
the Monday times are not applicable for 
the whole week, then the exceptional days 
would need to be reprogrammed to the 
desired schedule.
To program the chiller for 24 hour operation, program 
the start and stop times of each day of the week for 
00:00.
After the SUN (Sunday) schedule appears on the dis-
ARROW) key will display the Holiday schedule. This 
is a two-part display. The first reads:
SCHEDULE  UNIT OPERATING
HOL  START = 00:00 AM STOP = 00:00 PM               
The holiday times may be set using the same procedure 
as described above for the days of the week. Be sure to 
press the  (ENTER) key after setting the START and 
STOP times to save the change in memory. Pressing 
the SCHEDULE key a second time, the display will 
show the individual days:
SCHEDULE  UNIT OPERATING
S  M  T  W  T  F  S   HOLIDAY NOTED BY  *
The line below the empty space is the cursor and will 
     
pressed. To set a day for the Holiday Schedule, the cur-
sor must be moved to the space following the day of 
the week. The * key is then pressed and an “*” will 
appear in the space signifying that day as a holiday. 
The Holiday schedule must be programmed weekly. If 
there is no holiday, the “*” key is also used to delete the 
“*”. The  (ENTER) key is used to accept the holiday 
schedule for the entire week.
The HOLIDAY SCHEDULE is a tem-
porary schedule. Once the schedule is 
executed, the selected holidays will be 
cleared from memory for the following 
week.
Sound limit schedule
The SOUND LIMIT SCHEDULE allows setting the 
day and time when the user desires using the “SILENT 
NIGHT” factory programmed option to limit chiller 
loading and fan operation for reduced audible noise in 
the surrounding area. If the SOUND LIMIT SCHED-
ULE is selected under the CHOOSE SCHEDULE dis-
play, the following message will appear:
SCHEDULE  SOUND LIMIT  = XXX %
MON  START = 06:00 AM     STOP = 10:00 PM               
The Sound Limit option can be enabled and disabled 
once each day or the chiller can be set to run continu-
ously in this mode for sound limiting whenever the 
chiller is operating. When sound limiting is enabled, 
the unit will be limited by the Sound Limit setpoint 
% as set under the PROGRAM key. XXX in the dis-
play above will show the Sound Limit Setpoint % pro-
grammed under the PROGRAM key. 0% will cause no 
speed reduction, while 100% only allows running at 
minimum speed.
The START Time for a specific day (hour and minute) 
is entered using the same guidelines used for the start/
stop schedules, and press the  (ENTER) key to store 
it into memory. The cursor will then move to the AM/
PM selection. 
        
     
pressing  (ENTER) key to store the value. 
This process is repeated for the STOP time. 
Once the schedule for a specific day is programmed 
and entered, the schedule for the next day will appear. 
The schedule for each day may be programmed the 
same or differently.
To view the schedule without changing it, simply press 
key will scroll backwards to the previous screen.