SECTION 8 - MICROPANEL
JOHNSON CONTROLS
163
Form  201.28-NM1.1
Issue date: 08/06/2021
8
CONDENSER FANS ON   0
CONDENSER FAN SPEED  XXX % (vsd)
COMPRESSOR HEATER   ON
VI STEP SOLENOID 1  OFF
VI STEP SOLENOID 2  OFF
RUN PERMISSIVE    ON
VSD RUN RELAY    OFF
VSD SOFTWARE RUN SIGNAL  OFF
SYSTEM 2 DATA
COMPRESSOR STATUS   ON
RUN TIME    0-0-15-26 D-H-M-S
MOTOR CURRENT  104 AMPS  87 %FLA
SUCTION PRESSURE      57 PSIG
DISCHARGE PRESSURE    233 PSIG
OIL PRESSURE      218 PSIG
CONDENSER LIQUID TEMP    42.9 DEGF
DISCHARGE TEMPERATURE    145.5 DEGF
SAT CONDENSER TEMP    31.7 DEGF
SUBCOOLING   11.2 DEGF
SAT DISCHARGE TEMP    112.1 DEGF
DISCHARGE SUPERHEAT    33.4 DEGF
MOTOR TMP    XXX.X XXX.X XXX.X DEGF
COMPRESSOR SPEED      XXX.X%
FLASH TANK LEVEL      < 512 ADC
COND DRAIN % OPEN        XXX.X%
ECONOMIZER % OPEN        XXX.X%
CONDENSER FANS ON     3
CONDENSER FAN SPEED    XXX% (vsd)
COMPRESSOR HEATER     OFF
VI STEP SOLENOID 1  OFF
VI STEP SOLENOID 2  OFF
RUN PERMISSIVE      ON
VSD RUN RELAY      OFF
VSD SOFTWARE RUN SIGNAL   OFF
UNIT OPERATING SCHEDULE
S  M  T  W  T  F  S    *=HOLIDAY
MON START=00:00AM   STOP=00:00AM
TUE START=00:00AM   STOP=00:00AM
WED START=00:00AM   STOP=00:00AM
THU START=00:00AM   STOP=00:00AM
FRI START=00:00AM   STOP=00:00AM
SAT START=00:00AM   STOP=00:00AM
HOL START=00:00AM   STOP=00:00AM
SOUND LIMIT SCHEDULE 
(if enabled)
MON START=00:00AM   STOP=00:00AM
TUE START=00:00AM   STOP=00:00AM
WED START=00:00AM   STOP=00:00AM
THU START=00:00AM   STOP=00:00AM
FRI START=00:00AM   STOP=00:00AM
SAT START=00:00AM   STOP=00:00AM
HOL START=00:00AM   STOP=00:00AM
History data printout
History printouts, when selected, provide stored data 
relating to all specific system and chiller operating 
conditions at the time of the fault, regardless of wheth-
er a lockout occurred.  History information is stored in 
battery-backed memory on the Chiller Control Board 
and is not affected by power failures or resetting of 
faults.  Whenever a fault of any type occurs, all system 
operating data is stored in battery-backed memory at 
the instant of the fault. The history printout is similar 
to the operating data printout except for the change in 
the header information shown as follows:
YORK INTERNATIONAL CORPORATION
YVAA SCREW CHILLER
HISTORY NUMBER 1
2:04:14 PM  30 APR 11
SYS 1 YYYYYYY
HIGH DSCH PRESS SHUTDOWN
STATUS AT TIME OF SHUTDOWN
SYS 1 XXXXXXXXXXXXXXXXXXXXXXXXXX
SYS 2 XXXXXXXXXXXXXXXXXXXXXXXXXX
ALL FAULTS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
The most recent fault will always be stored as 
HISTORY BUFFER #1.