EasyManua.ls Logo

York YVAA Style A - Unit Rigging Specifications (Continued); Rigging Hole Locations (Continued)

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 3 - RIGGING, HANDLING, AND STORAGE
JOHNSON CONTROLS
27
Form 201.28-NM1.1
Issue date: 08/06/2021
3
LD18582
Table 1 - Unit rigging (cont'd)
YVAA model
Description Units
Rigging holes
Frame Cond Evap I J K L M N O P
015 3 B
Rigging hole
location
in. 18 60 116 192
mm 464 1511 2937 4866
016 5 B
Rigging hole
location
in. 18 60 137 214
mm 464 1533 3485 5435
017 8 C
Rigging hole
location
in. 12 73 144 197 260
mm 314 1845 3654 5012 6593
018 3 A
Rigging hole
location
in. 18 60 143 220
mm 464 1533 3636 5598
019 5 A
Rigging hole
location
in. 18 60 143 227 272
mm 464 1533 3636 5761 6920
019 8 B
Rigging hole
location
in. 18 60 137 215 302
mm 464 1533 3484 5455 7670
020 0 C
Rigging hole
location
in. 60 131 214
mm 1518 3332 5430
021 3 A
Rigging hole
location
in. 18 60 143 227 272
mm 464 1533 3637 5761 6920
021 5 C
Rigging hole
location
in. 12 73 144 197 260
mm 314 1845 3654 5012 6593
021 8 C
Rigging hole
location
in/ 12 73 163 254 324
mm 314 1845 4144 6443 8218
Note: Rigging and lifting the unit must be done safely by a professional rigger as discussed in this section. The rigger should locate the center of
gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Johnson Controls Sales O󰀩ce for weight data.

Table of Contents