EasyManua.ls Logo

York YVAA Style A - Optional One-Pass Evaporator Dimensions (Continued); Evaporator Dimensions and Flow Rates (Continued)

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
71
Form 201.28-NM1.1
Issue date: 08/06/2021
5
Table 7 - Optional one-pass evaporator (cont'd)
All dimensions - in. (mm)
YVAA
A,B C D E-nozzle size
Water volume gal
(L)
Minimum chilled
water ow rate
GPM (L/S)
Maximum chilled
water ow rate
GPM (L/S)
Frame
Cond.
23 3
20.8
(528)
73.2
(1859)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
24 5
21
(533)
92.9
(2360)
56.1
(1425)
8
71
(269)
590
(37)
2190
(138)
24 8
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
26 3
21
(533)
117.1
(2974)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
27 0
21
(533)
16.8
(427)
51.9 (1318) 8
82
(310)
590
(37)
2190
(138)
27 3
21
(533)
42.9
(1090)
70
(1778)
8
82
(310)
590
(37)
2190
(138)
27 5
22.5
(572)
44.7
(1135)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
27 8
22.5
(572)
88.3
(2243)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
29 5
22.5
(572)
88.6
(2250)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
30 3
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permittted. Glycol limits are higher. Contact your Johnson Controls Sales O󰀩ce for ratings and further information.

Table of Contents