SECTION 6 - OPERATION
UNIT DATA KEY
UNIT
DATA KEY
FIGURE 49 - UNIT DATA KEY
The UNIT DATA key displays unit temperatures, and
related data. Select the displays, which are listed se-
quentially, by repeatedly pressing the UNIT DATA, or
the ▲ or ▼ key.
UNIT CHILLED LIQUID LEAVE = ###.# °F
ENTER = ###.# °F
UNIT CONDENSER LIQUID LEAVE = ###.# °F
ENTER = ###.# °F
UNIT LOAD TIMER = ### SEC
UNLOAD TIMER = ### SEC
UNIT TEMP ERROR = ###.# °F
RATE = ###.# °F/M
The message (above) displays the error in temperature
between the actual leaving chilled liquid and setpoint
temperatures. RATE = ###.#°F/M shows the rate of
change of the chilled liquid temperature.
UNIT LEAD SYSTEM NUMBER = 1 OR 2
UNIT CHILLED LIQUID FLOW SW = ON OR OFF
CONDENSER LIQUID FLOW SW = ON OR OFF
UNIT EVAP/COND PUMP RUN = ON OR OFF
VSD COOLANT AUX PUMP = ON OR OFF
If the control is enabled, the VSD coolant aux pump
messages will display ON or OFF.
UNIT ACTIVE REMOTE CONTROL = ACTIVE OR NONE
TYPE: BAS CURR TEMP MODE
If ACTIVE REMOTE CONTROL is NONE, the items
on the second line (TYPE) are blank. If ACTIVE RE-
MOTE CONTROL is ACTIVE, the following items
will be displayed, and are listed below:
• NONE - No remote control is active; however, re-
mote monitoring may be active.
• BAS - remote mode
• CURR - Remote Current Limiting is enabled.
• TEMP - Remote Temperature Reset is enabled.
• MODE - Remote MODE SELECT (REMOTE
MODE).