JOHNSON CONTROLS
115
SECTION 6 - OPERATION
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
6
SETUP MODE ◄DEF 2.0 LO 0.1 HI 10.0
LVL CTRL INCREMENT 1 SETP = ##.# %
SETUP MODE ◄DEF 0.5 LO 0.1 HI 10.0
LVL CTRL INCREMENT 2 SETP = ##.# %
SETUP MODE ◄DEF 0.7 LO 0.5 HI 3.0
LEVEL CNTRL STARTUP KP = #.#
SETUP MODE ◄DEF 115 LO 75 HI 250
LEVEL CNTRL STARTUP TN = 115 SEC
SETUP MODE SMART FREEZE
◄► DISABLED
SETUP MODE OIL PUMP
◄► DISABLED
SETUP MODE OIL LEVEL SW
◄► DISABLED
SETUP MODE VSD AUX COOLANT PUMP
◄► DISABLED
SETUP MODE HOT GAS BYPASS
◄► DISABLED
SETUP MODE ◄DEF 0.0 LO 0.0 HI 2.0
HOT GAS BYPASS SETP OFFSET = #.# °F
SETUP MODE ◄DEF 1.0 LO 1.0 HI 5.0
HOT GAS BYPASS SETP = #.# °F
SETUP MODE ◄DEF 30 LO 5 HI 50
COND VLV STARTUP POS = ## %
SETUP MODE ◄DEF 5 LO 0 HI 10
COND VLV CTRL START DLY = ## MIN
SETUP MODE REFRIG INJ
◄► ENABLED
SETUP MODE VI STEP VALVE
◄► ENABLED
SETUP MODE ◄DEF 195.0 LO 195.0 HI 333.0
HIGH DISCHARGE PRESS CUTOUT = ###.# PSIG
SETUP MODE COMPRESSOR TYPE
◄► XXXXXXX
SETUP MODE DROP LEG REFRIG TEMP SENSOR
◄► DISABLED
SETUP MODE CONDENSER PRESSURE SENSOR
◄► DISABLED
SETUP MODE EVAP REFRIG TEMP SENSOR
◄► DISABLED
SETUP MODE UNIT SOFT SHUTDOWN OPERATION
◄► DISABLED
SETUP MODE SKIP FREQ 1
◄► DISABLED
SETUP MODE ◄DEF 56 LO 50 HI 199
SKIP FREQ 1 LOW LIMIT = ### HZ
SETUP MODE ◄DEF 68 LO 57 HI 68
SKIP FREQ 1 HIGH LIMIT = ## HZ
SETUP MODE SKIP FREQ 2
◄► DISABLED
SETUP MODE ◄DEF 88 LO 70 HI 202
SKIP FREQ 2 LOW LIMIT = ### HZ
SETUP MODE ◄DEF 100 LO 89 HI 100
SKIP FREQ 2 HIGH LIMIT = ### HZ
SETUP MODE LINE VOLTAGE
◄► ### V
SETUP MODE ◄DEF 160.5 LO 160.5 HI 535.0
JOB FULL LOAD AMPS = ###.# AMPS