34
MODGAS-XWR2 Technical Guide
LCD SCREENS
Conguration Screens
MOD CNFG
xVyIGNzS
MODULATION CONFIGURATION
Values are in the format xVyIGNzS, where x is the number of valves
(V), y is the number of ignitors (IGN) and z is the number of stages
(S). Values are 1V1IGN1S, 2V2IGN2S, 2V1IGN1S, and 2V2IGN1S.
Default is 1V1IGN1S.
The four congurations are explained in detail as follows:
1V1IGN1S: Valve conguration used to control one modulating gas
valve, which must be placed on the gas valve 1 header (attached to
Heat 1 Relay). Additional stages may be added to Heat Relays 2, 3
and4, or o board if in a communication mode.
2V1IGN1S: Valve conguration used to control two modulating
gas valves (one on each header), in which the rst and second
valves operate together for one modulating stage. Both valves are
connected to Heat 1 Relay, therefore, an additional xed stage may
be added on board at the Heat 2 Relay. Additional stages may be
added on Heat Relays 3 and 4 or o board for this conguration if it is
in a Communications Mode. NOTE: Since both valves are attached
to Heat 1 Relay, only one proof of ame is required for both valves.
2V2IGN1S: Valve conguration used to control two modulating gas
valves (one on each header), in which the rst and second valves
operate together for one modulating stage. One valve is connected
to Heat 1 Relay and the second valve is connected to Heat 2 Relay.
Additional stages may be added to Heat Relays 3 and 4 or o board if
it is in a Communications Mode.
2V2IGN2S: Valve conguration used to control two modulating gas
valves (one on each header), in which the rst valve is modulating
stage 1 (valve 1 header) and the second valve is modulating stage
2 (valve 2 header). Additional stages may be added to Heat 3 and 4
Relays or o board if it is in a Communications Mode.
STG DOWN
DLY 1
STAGE DOWN DELAY
Range is 1 to 10 minutes. Default is 1.
STG UP
DLY 1
STAGE UP DELAY
Range is 1 to 10 minutes. Default is 3.
IGN RTRY
DLY XX m
IGNITION RETRY DELAY
Range is 1-60 minutes. Default is 30
TMP SCL
FAHRENHT
TEMPERATURE SCALE
Fahrenheit (default) or Celsius.
This setting is only used in Stand-Alone Mode.
VLV STRT
POS XX%
VALVE START POSITION
Range is 55-100% in 5% increments. Default is 70%.
LOSAT SU
XX°F
LOW SUPPLY AIR TEMPERATURE START-UP
Range is 0ºF-45ºF. Default is 40ºF
If the Supply Air Temperature is less than the dened value, the
stage up delay is reduced from three minutes to one minute.
St@MinDb
XXº
MIN MODE DEADBAND
Range: 0-30 degrees.
NOTE: If it is set to 0, Min Mode will not initialize and the sequence
will continue to Heating Mode.
MinPosTP
XXXs
MIN MODE RUN TIME
Range: 0-500 seconds.