124
RN Series Startup Form
Job Name:___________________________________________________________________
Address:_____________________________________________________________________
___________________________________________________________________________
Model Number:_______________________________________________________________
Serial Number:__________________________________________
Startup Contractor:____________________________________________________________
Address:_______________________________________________
______________________________________________________
Installing contractor must verify the following items.
1. Is there any visible shipping damage?
3. Are the unit clearances adequate for service and operation?
4. Do all access doors open freely and are the handles operational?
5. Have all electrical connections been tested for tightness?
6. Does the electrical service correspond to the unit nameplate?
7. On 208/230V units, has transformer tap been checked?
8. Has overcurrent protection been installed to match the unit nameplate
requirement?
9. Have all set screws on the fans been tightened?
10. Do all fans rotate freely?
11. Is all copper tubing isolated so that it does not rub?
12. Has outside air rain hood been opened?
13. Have the damper assemblies been inspected?
14. Are the air filters installed with proper orientation?
15. Have condensate drain and p-trap been connected?
Band Size_____________________
VAV Controls_________________
VFD Frequency________________