OVERVIEW
4
RSMD Technical Guide
Features & Applications
The OE370-26-RSMD Refrigerant System Module for Digital
Compressors (RSMD) (AAON Part No: V61520) can monitor and
control up to two compressors and condensers. The compressors can
be in either a tandem or non-tandem confi guration. The module is
designed for R410-A refrigerant.
The RSMD is connected to the VCC-X / VCCX2 Controller.
Up to 4 RSMD’s can be connected, depending on the size of the
system. There are 2 E-BUS Expansion Ports which allow the use of
communicating sensors and the E-BUS Modules.
The RSMD provides 3 analog inputs, 4 binary inputs, 5 relays, and
2 analog outputs. See Figures 2 & 3, pages 6 & 7 for wiring.
The RSMD Module provides the following:
Modulates the Compressors to satisfy the Suction
Coil (Saturated) Temperature. The Suction Coil (Satu-
rated) Temperature Setpoint is reset by the VCC-X /
VCCX2 Controller to maintain the Supply Air
Temperature during Cooling mode. During Dehumidi-
cation mode, it controls the Compressors to the
Suction (Saturation) Temperature Setpoint.
In Heating mode, the RSMD modulates and stages
the compressors to maintain a given Supply Air
Temperature Setpoint.
Modulates the Condenser Fan or Valve to maintain
the Head Pressure Setpoint.
Provides alarms and safeties for the Compressor and
Condenser operation.
Allows connection of the Modular Service Tool SD
to the module when required communication wire is
run to the VCC-X / VCCX2 Controller.
Provides a 2 x 8 LCD character display and 4 buttons
that allow for status of system operation, system
setpoints, system con gurations, sensors, and alarms,
and to change the modules address, if necessary.
RSMD Overview