76 Installation
syd-0210/1.7 – I7.9 – 12.2009
4. 4. 2 Uninterruptible power supply (UPS)
The use of an external uninterruptible power supply (UPS) guarantees operation
even in the event of a mains outage.
The UPS battery capacity is rated according to the systems power requirements
and the required bridging time. The table below shows the required battery capac-
ity for a battery voltage of 12 V.
Tab. 21 Power requirements of an A150/300 and battery rating (12 V)
Note
The uninterrupted operation of the system is ensured if the UPS takes
over the power supply within 6 ms of the mains outage.
See also
For more technical details see "Technical Data", page 217.
System
Maximum power require-
ments
Battery capacity [Ah]
1)
for bridging time
1)
Maximum configuration and maximum traffic volume. Typical conditions require approx. 60% of the speci-
fied battery capacity
OCW1 h4 h12 h
A150 100 50 7 28 84
A300 150 75 11 44 132