Appendix C MODBUS® register lists
266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB | 89
Register Address
Data
Type
Object description
Read/
Write
Added
Ext.
32 bit
16 bit
210
211
1001-1004
Char
Display line 1, 8 ASCII characters per line.
Protection see 492
Write protection Dip Switch does not protect this register.
R/W
212-213
1005-1008
Char
Display line 2, 8 ASCII characters per line.
Protection see 492
Write protection Dip Switch does not protect this register.
R/W
214-218
1009-1018
Char
Display Tag 1 line, 20 ASCII characters per line.
Protection see 492
Write protection Dip Switch does not protect this register.
R/W
Customer Diagnostic Limits
5541
5041 5042
F
DP URV, Upper Range Value (default set to URL)
R/W
5542
5043 5044
F
DP LRV, Operating Lower Range Value (default set to LRL)
R/W
5543
5045 5046
F
SP URV, Operating Upper Range Value (default set to URL)
R/W
5544
5047 5048
F
SP LRV, Operating Lower Range Value
(default set to 0.0697 MPa ~1 atm @ 10000 ft ~10.1 psi )
R/W
5545
5049 5050
F
Transducer cell Temperature Operating Upper Range Value
R/W
5546
5051 5052
F
Transducer cell Temperature Operating Lower Range Value
R/W
5547
5053 5054
F
RTD Temperature Operating Upper Range Value
R/W
5548
5055 5056
F
RTD Temperature Operating Lower Range Value
R/W
Customer Max / Min Values
5549
5057 5058
F
DP Maximum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5550
5059 5060
F
DP Minimum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5551
5061 5062
F
SP Maximum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5552
5063 5064
F
SP Minimum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5553
5065 5066
F
Transducer Temperature Maximum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5554
50675068
F
Transducer Temperature Minimum measured value
Write always sets value to current measurement, the value from the write request
is ignored.
R/W
5555
50695070
F
RTD Maximum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
5556
50715072
F
RTD Minimum measured value
Write always sets value to current measurement; the value from the write request
is ignored.
R/W
Service Max value ever measured
5557
50735074
F
DP Maximum ever measured value
RO
5558
50755076
F
DP Minimum ever measured value
RO
5559
50775078
F
SP Maximum ever measured value
RO
5560
50795080
F
SP Minimum ever measured value
RO