Appendix C MODBUS® register lists
90 | 266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
Transducer Temperature Maximum ever measured value
Transducer Temperature Minimum ever measured value
RTD Maximum ever measured value
RTD Minimum ever measured value
Customer Operating Range Alarm Levels
DP Above URV Alarm Set at this level (in DP units) referenced to register 5541
=’s URV + ((URV-LRV) * DPHysteresis * 0.01 )
DP Below LRV Alarm Set at this level (in DP units) referenced to register 5542
=’s LRV - ((URV-LRV) * DPHysteresis * 0.01)
DP Below URV Alarm Clears at this level (in DP units) referenced to register 5541
=’s URV - ((URV-LRV) * DPHysteresis * 0.01 / 2)
DP Above LRV Alarm Clears at this level (in DP Units) referenced to register 5542
=’s LRV + ((URV-LRV) * DPHysteresis * 0.01 / 2)
DP Alarm Hysteresis Percent of User Range Span referenced to register 5541 &
5542 (default 2%)
(DPHysteresis)
SP Alarm Hysteresis Percent of User Range Span referenced to register 5543 &
5544 (default 2%)
(SPHysteresis)
SP Above URV Alarm Set at this level (in SP units) referenced to register 5543
=’s URV + ((URV-LRV) * SPHysteresis * 0.01 )
SP Below LRV Alarm Set at this level (in SP units) referenced to register 5544
=’s URV - ((URV-LRV) * SPHysteresis * 0.01 )
SP Below URV Alarm Clears at this level (in SP units) referenced to register 5543
=’s LRV - ((URV-LRV) * SPHysteresis * 0.01 / 2)
SP Above LRV Alarm Clears at this level (in Sp Units) referenced to register 5544
=’s LRV + ((URV-LRV) * SPHysteresis * 0.01 / 2)
Measurements Bias Parameters
DP bias value is being added to the DP measurement producing an overall offset
adjustment.
SP bias, see preceding register for discussion.
Set DP to a value, units are same as the DP measurement.
DP bias = value – current measurement.
This results in the reported value in register 401-402 to be the value.
Set SP to value, see preceding register for discussion.
Reset DP Bias, sets the bias value to zero, effectively removing any effects of bias
on DP measurement.
This is an action register and the data value has no meaning.
Reset SP Bias, sets the bias value to zero, see preceding register.
Informative / Maintenance (Available in all Modbus mapping modes)
Modbus mapping selection:
0 = ABB map
1 = Rosemont map
2 = Invensys map
Date and time the CB firmware was built. Julian date number of seconds since Jan
01, 1970 00:00:00