8.3 Loose Part Delivery and CE-marking
If an Advant Controller 450 is ordered as a loose part delivery and the intention is to mount the
equipment in other cabinets than RM500, certain considerations must be taken to make it follow
the provisions of the EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC.
The cabinet or series of cabinets mounted side by side must be EMC-proof.
Protection against line conducted radio emissions is obtained by means of a mains net
filter placed in the cabinet close to the incoming mains cable.
Communication cable shields must have a capacitive grounding at the point where they
enter the cabinet.
The conditional EC - Declaration of Conformity, which accompanies the loose part delivery,
must be signed by the person responsible for assembling the controller in cabinets.
8.4 Non Standard Program Modules
The item Loading of BU/BA specific program module in Table 8-7 gives a possibility to add
a non standard program module to the standard modules on the system software program card.
Certain conditions must be fulfilled and a special reference number must be used when
ordering. Please contact our regional Sales Department for further information.
8.5 Heat Exchanger
With sealed cabinets (protection class IP54) it can be necessary to use a heat exchanger to keep
the temperature low in the cabinet. To make power loss calculations, all necessary information,
like power loss for each board/module/unit in the cabinet and figures for maximum power loss
in the cabinet, is found in the Advant Controller 450, Users Guide.
8.6 Reference Guide
Please see the current price list.