EasyManua.ls Logo

ABB CoreSense - CoreSense Default Factory Values (Appendix G); Factory Parameter Defaults

ABB CoreSense
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX G
CoreSense default factory values
The table below contains all the values as they were configured at the factory.
Parameters Description Default value Details
Hydrogen
hydrogen.sensor-offset hydrogen sensor offset correction 0 See “Hydrogen settings”
on page 34.
hydrogen.slope-correction hydrogen slope correction 1.0
hydrogen.roc24h-trigger hydrogen rate of change over 24h trigger
(in ppm/day)
80
hydrogen.level-warning hydrogen level warning (in ppm) 100
hydrogen.level-critical hydrogen level critical (in ppm) 250
hydrogen.roc24h-warning hydrogen rate of change 24h warning 10
hydrogen.roc24h-critical hydrogen rate of change over 24h critical 25
Moisture
moisture.sensor-offset moisture sensor offset correction 0 See “Moisture settings”
on page 35.
moisture.slope-correction moisture slope correction 1
moisture.level-warning moisture level warning (in ppm) 20
moisture.level-critical moisture level critical (in ppm) 30
moisture.roc24h-trigger moisture rate of change over 24h trigger
(in ppm/day)
15
moisture.roc24h-warning moisture rate of change over 24h warning 5
moisture.roc24h-critical moisture rate of change over 24h critical 10
moisture.oil-A moisture oil A 1666.33
moisture.oil-B moisture oil B 7.36
System
system.settings-changes-
allow-on-all-interfaces
Boolean:true See “Communication
settings” on page 37.
system.h2-420-min Integer:0 # Hydrogen 420 value for 4 mA 0
system.h2-420-max Integer:1000 # Hydrogen 420 value for 20 mA 1000
system.h2o-420-min Integer:0 # Moisture 420 value for 4 mA 0
system.h2o-420-max Integer:80 # Moisture 420 value for 20 mA 80
Hardware
hardware.modbus-tcp-port Integer:502 502
hardware.dnp3-tcp-port Integer:20000 20000

Table of Contents