IEC 61850 (CoreSense only)   E95
SIML
DO Name CDC Explanation M/O/C/E Remarks
H2RoCWrn SPS Hydrogen rate of change warning E
MstRoCWrn SPS Moisture rate of change warning E
Settings
H2AlmSpt ASG Hydrogen alarm set point E
MstAlmSpt ASG Moisture sensor alarm set point E
H2RoCAlmSpt ASG Hydrogen rate of change alarm set point E
MstRoCAlmSpt ASG Moisture rate of change alarm set point E
H2WrnSpt ASG Hydrogen warning set point E
MstWrnSpt ASG Moisture sensor warning set point E
H2RoCWrnSpt ASG Hydrogen rate of change warning set point E
MstRoCWrnSpt ASG Moisture rate of change warning set point E
PICS
ACSI Basic Conformance Statement
The basic conformance statement is defined in the following table.
Client/ 
Subscriber
Server/ 
Publisher
Value/ 
Comments
Client-Server Roles
B11 Server side (of TWO-PARTY-APPLICATION-ASSOCIATION)  Y
B12 Client side of (TWO-PARTY-APPLICATION-ASSOCIATION)  -
SCSMs Supported
B21 SCSM: IEC 61850-8-1 used  Y
B22 SCSM: IEC 61850-9-1 used  N Deprecated 
Ed2
B23 SCSM: IEC 61850-9-2 used  N
B24 SCSM: other  N
Generic Substation Event Model (GSE)
B31 Publisher side  N
B32 Subscriber side  -
Transmission of Sampled Value Model (SVC) 
B41 Publisher side  N
B42 Subscriber side  -
- = not applicable
Y = supported
N or empty = not supported