APPENDIX C
Modbus table
The RS-485 and Modbus default settings can be modified using the web interface.
NOTICE
For best results it is recommended to configure the Modbus master with a timeout of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The default slave ID is 1.
Default RS-485 configuration
Baud rate 9600
Data Bits 8
Stop bits 1
Parity None
Flow control None (only none is supported)
Default TCP configuration port
Modbus TCP 502/tcp