E84 Installation Guide
ID ED Description Value/Clarification
As7 1,2 What is the maximum and minimum MMS PDU size Max MMS PDU size 120000
bytes
Min MMS PDU size 1200 bytes
As8 1,2 What is the maximum start up time after a power supply
interrupt
5 minutes
As9 1,2 Does this device function only as test equipment?
(test equipment need not have a non-volatile configuration; but
it cannot be part of the substation automation system)
No
PIXIT for Server Model
ID ED Description Value/Clarification
Sr1 1,2 Which analogue value (MX) quality bits are supported (can be set by
server)
Validity:
Good Y
Invalid Y
Reserved N
Questionable Y
Overflow N
OutofRange N
BadReference N
Oscillatory N
Failure Y
OldData N
Inconsistent N
Inaccurate N
Source:
Process Y
Substituted Y
Test N
OperatorBlocked N

Table of Contents