48 Installation Guide
Q. Cannot connect to the web interface on the service port
A. Make sure that you are connected to the service port and not the SCADA port. On your laptop or
PC, verify in your Ethernet settings that your IP address is set to Automatic. The CoreSense service
port is configured by default as a DHCP server and it will assign an IP address in the 172.16.100.10 to
172.16.100.20 range. This could take a few minutes.
Verify that the CoreSense responds to a ping at 172.16.100.1