B66 Installation Guide
Register Modbus
address
Parameter Function Data type Access
59 40059 Moisture (ppm) signed 16 bit binary number R
60 40060 Moisture
(ppm/day)
may need scaling signed 16 bit binary number R
61 40061 RESERVED–Moisture
(ppm/week)
return 0 signed 16 bit binary number R
62 40062 RESERVED–Moisture
(ppm/week)
return 0 signed 16 bit binary number R
63 40063 4–20 mA input 1 scaled by 100 signed 16 bit binary number R
64 40064 4–20 mA input 2 scaled by 100 signed 16 bit binary number R
65 40065 4–20 mA input 3 scaled by 100 signed 16 bit binary number R
Status/Alarms
66 40066 Status and alarms <See status table > 16 bit binary map R
Calculated Values
67 40067 Aging signed 16 bit binary number R
68 40068 Hotspot signed 16 bit binary number R
69 40069 Load Ratio signed 16 bit binary number R
70 40070 Loss of Life signed 16 bit binary number R
71 40071 Overload Capacity 5 minutes signed 16 bit binary number R
72 40072 Overload Capacity 15
minutes
signed 16 bit binary number R
73 40073 Overload Capacity 30
minutes
signed 16 bit binary number R
74 40074 Overload Capacity 60
minutes
signed 16 bit binary number R
75 40075 Overload Capacity 120
minutes
signed 16 bit binary number R
Configuration
76–200 Reserved for future use
Generic Modbus sensor 1
201 40201 Generic modbus sensor
corrected value
signed 16 bit binary number signed 16 bit binary number R
202 40202 Reserved R
203 40203 Reserved R
204 40204 Generic modbus sensor
status
See < Generic Modbus
Sensor Status Table >
signed 16 bit binary number R
205-210 Reserved R
Generic modbus sensor 2
211
40211
Generic Modbus sensor
corrected value
signed 16 bit binary number
signed 16 bit binary number
R
212 40212 Reserved R
213 40213 Reserved R