CoreSense Hub option B75
eDevice Sensor name Dev. ID¹ Dev. ID
range
Reg. Unit Slope Bias En. 24h
avrgin
Upper
alarm²
Upper
warn.²
Lower
warn.²
Lower
alarm²
eWTI – Winding
temp.
111 96–111 8192 °C 1 o NO 90 80 20 0
SDB10 OLTC –
Salts saturation
1 1–16 8192 % 1 o NO – – – –
SDB15 Main tank
– Salts saturation
1 1–16 8192 % 1 o NO – – – –
SDB30 Main tank
– Salts saturation
1 1–16 8192 % 1 o NO – – – –
SDB40 Main tank
– Salts saturation
1 1–16 8192 % 1 o NO – – – –
SDB10C OLTC –
Salts temp.
175 160–175 106 °C 0.1 o NO – – – –
SDB12C OLTC –
Salts temp.
175 160–175 106 °C 0.1 o NO – – – –
SDB14C Main
tank – Salts temp.
175 160–175 106 °C .01 o NO – – – –
¹ See specific eDevice instruction sheet to change the Device ID in case more than one device of the same
type is installed on the transformer.