Section-10
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc Page 5/16 ABB
Modifications reserved
DPA UPScale RI
unit
UPScale RI 40
DPA UPScale RI Subrack
Configuration
accommodates:
Max.
4 modules (10 or 20kW)
Max. Subrack connection
kW
80
Dimensions (WxHxD)
mm
448x798x735 (18 HU)
482
1)
x798x735 (18 HU)
Weight of Empty Frame
w/o modules and
w/o batteries
kg
50
Weight of Frame with
modules and w/o batteries
kg
124 up to 136
(with 4 Modules)
Module type
unit
UPScale M 10
UPScale M 20
Module rated power
kW
10
20
Allowed nr. VRLA 12V
battery blocks
No.
20
2)
- 50
30
2)
- 50
Dimensions (WxHxD)
mm
482
1)
x 132 x 540 (3HU)
Weight
kg
18.6
21.5
Colors
Front : RAL 9005
Approximate
3)
audible
noise at 1m from front, of
one module only.
100% / 50% Load
dBA
55
3)
/ 49
3)
57
3)
/ 49
3)
Notes:
1)
482 mm is the width including the wings in the front.
2)
Depending of the effective load in kW used by the module (see chapter 10.4 Battery Characteristics)
3)
These are approx. figures and of one module only. The audible noise depends also on the cabinet which host the
subracks.

Table of Contents