Section-2
04-3006_S2_OPM_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc Page 2/14 ABB
Modifications reserved
2.1 BLOCK DIAGRAM
2.1.1 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel
such as a licensed service engineer from the manufacturer or from an agent certified by the manufacturer.
2.1.2 RECOMMENDED CABLE SECTIONS & FUSE RATINGS
2.1.2.1 Terminal connections overview
FRAME TYPE
Terminals (T)
Connection Bar (B)
Battery Earth
PE
Separate. Battery
(+ / N / - )
Common
Battery
(+ / N / - )
Input Bypass
3+N
Input Rectifier
3+N+PE
Output load
3+N+PE
UPScale RI 10
16/25mm
2
(T)
3 x 10/16mm
2
(T)
n.a
4 x 10/16 mm
2
(T)
5 x 10/16 mm
2
(T)
5 x 10/16 mm
2
(T)
UPScale RI 11
n.a.
n.a.
n.a.
UPScale RI 12
n.a.
n.a.
n.a.
UPScale RI20
16/25mm
2
(T)
2x
(3 x 10/16mm
2
) (T)
3 x M5 (B)
4 x 16/25 mm
2
(T)
5 x 16/25 mm
2
(T)
5 x 16/25 mm
2
(T)
UPScale RI 22
n.a.
n.a.
n.a.
UPScale RI 24
n.a.
n.a.
n.a.
UPScale RI40
50 mm
2
(T)
4x
(3 x 10/16mm
2
) (T)
3 x M6 (B)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
+PE 50 mm
2
(T)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
+PE 50 mm
2
(T)
n.a. = not allowed
UPScale RI 11, RI 12, RI 22, RI 24
(on rear site)
UPScale RI 10 UPScale RI 20
(on rear site) (on rear site)
UPScale RI 40
(on rear site)
Batt. Input Output
Batt. Input Output
Batt. Input Output
Input Output