Section-10
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc Page 6/16 ABB
Modifications reserved
10.3 INPUT CHARACTERISTICS
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input Voltage Tolerance
(ref to 3x400/230V) for Loads in %:
(-20%/+15%) 3x308/184 V to 3x460/264 V for <100 % load
(-26%/+15%) 3x280/170 V to 3x460/264 V for < 80 % load
(-35%/+15%) 3x240/150 V to 3x460/264 V for < 60 % load
Total harmonic distortion (THDi)
Max. input power with rated output power
(cosphi = 1.0), rated input voltage and
charged battery per Module
Max. Input Current with rated output
power (cosphi = 1.0), rated input voltage
and charged battery per Module
Max. Input Power with rated output power
(cosphi = 1.0), rated input voltage and
discharged battery per Module
Max. Input Current with rated output power
(cosphi = 1.0), rated input voltage and
discharged battery per Module
10.4 BATTERY CHARACTERISTICS
Maintenance free VRLA or NiCd
Allowed nr. VRLA 12V battery blocks
Allowed nr. of 1.2V NiCd cells
Maximum charging current per module
Ripple free ; IU (DIN 41773)
Standard (temp. sensor optional)
Automatic and periodically (adjustable)
2)
Depending of the effective autonomy (see table here below)
5 min autonomy: min. number of 12V batt. blocks
any autonomy: min. number of 12V batt. blocks