Section-10
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc Page 16/16 ABB
Modifications reserved
10.12.4 DUAL FEED INPUT
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
10.12.5 Dual FEED INPUT / Cable Sections
Enclosure
type
Load
in KW
Input 3x400V/230V
Bypass
3x400V/230V
Output
3x400V/230V
@ cosphi 1.0
Battery
Fuse B
(Agl/CB)
Cable B
(mm
2
)
(IEC 60950-1)
Max. Input
Current
with battery
charging
(A)
Fuse C
(Agl/CB)
Cable C
(mm
2
)
(IEC
60950-1)
Cable D
(mm
2
)
(IEC
60950-1)
I nom
Fuse E
+/N/-
(Agl/CB)
Cable E (mm
2
)
Only for external
Batteries
+ / N / -
Com.
Battery
Sep.
Battery
Upscale RI 10
20
3x40A
5x6
34
3x40A
4x6
5x6
29 A
3x63A
n.a
3x10
Upscale RI 11
20
3x40A
5x6
34
3x40A
4x6
5x6
29 A
3x63A
n.a
n.a
Upscale RI 12
20
3x40A
5x6
34
3x40A
4x6
5x6
29 A
3x63A
n.a
n.a
Upscale RI 20
40
3x80A
5x16
68
3x80A
4x16
5x16
58 A
3x100A *1
3x25 *1
2x(3x10)
Upscale RI 22
40
3x80A
5x16
68
3x80A
4x16
5x16
58 A
3x100A *1
n.a
n.a
Upscale RI 24
40
3x80A
5x16
68
3x80A
4x16
5x16
58 A
3x100A *1
n.a
n.a
Upscale RI 40
80
3x160A
5x50
136 A
3x160A
4x50
5x50
116 A
3x224A*1
3x95 *1
4x(3x10)
*1 only valid for common battery use
n.a = not allowed