Section-10
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc Page 7/16 ABB
Modifications reserved
10.5 OUTPUT CHARACTERISTICS
Module type
unit
UPScale M 10
UPScale M 20
Output rated apparent power (cosphi 0.8)
kVA
10
20
Output rated active power (cosphi 1.0)
KW
10
20
Output nominal current (In)
at 230VAC ph-N and cosphi 1.0
A
14.5
29
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < +/- 1%
Dynamic (Step load 0%-100% or 100%-0%) < +/- 4%
Output Voltage Distortion
%
With Linear Load < 1.5%
With Non-linear Load (EN62040-3:2001) < 3%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < +/- 2 %
(selectable for bypass operation) or < +/- 4 %
Free running +/- 0.1 %
Efficiency AC-AC (at cosphi 1.0)
(tolerance +/- 0.5% applies on all figures)
%
Load : 100% 75% 50% 25%
M20&M10 : 95.5 95.5 95 94.5
Bypass operation
At Nominal Input voltage of 3x400 V +/- 15%
or 190 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
%
100%
Phase Angle Tolerance
(With 100 % Unbalanced load)
°
< 2
Overload Capability on Inverter
%
125 % load 10 min.
150 % load 60 sec.
Output short capability on inverter (RMS)
A
3.0xIn during 40 ms
2.25xIn during 40 ms
Output short capability on static bypass
(RMS)
A
10xIn during 20 ms
Static bypass transfer time:
inverter bypass / bypass inverter / in
eco-mode
ms
<1 / <5 / <6
Crest Factor (Load supported)
3:1
10.5.1 GRAPH: AC AC EFFICIENCY with Linier load @ cosphi 1
Efficiency up to 1 % higher with output PF cosphi 0.8
Details refer to paragraph 10.7 Environmental Characteristics
Linear Load (cosphi=1)
95.5
95.5
95
94.5
70
75
80
85
90
95
100
25 50 75 100
Load %
%
UPS Module 10/20kW